Experimental Study Performance R-22 AC Split Retrofitted With Propane
Mechanical Engineering Department, Engineering Faculty, Diponegoro University Jl. Prof. Soedarto, SH, Tembalang, Semarang 50275, Indonesia
* Corresponding author: tanakaunlam@yahoo.co.uk
Refrigerant 22 or called R-22 is still the most widely used for air conditioners. However, since it has a relatively high global warming properties, the use of R-22 should be stopped. Refrigerant 290 briefed as R-290 (propane) is the type of refrigerant recommended by many experts for R-22 replacements because the global warming properties of R290 are much lower than R-22. Therefore, in this study the cooling capacity, flow rate mass, power consumed and COP will be evaluated. The air conditioner engine used in this research has 1 PK capacity which is redesigned by adding separator / ducting on various main components of AC. From the result of the study, there are several conclusions revealed: on the same compressor capacity, R-22 cooling capacity is still greater than R290. Meanwhile, the flow rate of R290 is lower than R-22. For power consumption from R-290, it is smaller than R-22. For the value of COP R-290, the value shows greater ie at R-290 on the variation of Incoming Temperature In Evaporator 20°C = 6.23, 23°C = 6.36, 25°C = 6.86, 29°C = 6.20. While at R-22, it shows 20°C = 5.36, 23°C = 6.02, 25°C = 5.76, 29°C = 6.335
© The Authors, published by EDP Sciences, 2018
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited. (http://creativecommons.org/licenses/by/4.0/).
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.