The Effect of Supply and Outdoor Air Temperature on The Enthalpy and Temperature Exchange Efficiency of a Paper Heat Exchanger
1 School of Computer Science and Engineering, Taylor’s University Lakeside Campus, 47500 Subang Jaya, Malaysia
2 Technology Research Department, Daikin Research & Development Malaysia Sdn. Bhd., 47000 Sungai Buloh, Malaysia
* Corresponding author: abdulkareem.mahdi@taylors.edu.my
Heat Recovery Ventilator (VHR) is widely used nowadays as it is capable to maintain high Indoor Air Quality (IAQ) while minimizing the energy loss of indoor air through air-to-air heat exchanger principle. The main component that enables VHR to perform air-to-air heat exchange is known as Paper Heat Exchanger (PP-HEX). Hence, the objective of this research is to study and analyse the performance of a PP-HEX under different return and outdoor air temperatures as well as their effect on both enthalpy and temperature exchange efficiency. Moreover, some numerical models of VHR have been developed to optimize some complex cases and the numerical models are meant to reduce the physical experiments to analyze or improve complex cases in the future. To the best of the authors knowledge, there is no experimental data available from any sources to validate the numerical models. To address this issue, two different supplies of PP-HEX are tested with an actual VHR, and both PP-HEXs will be referred to as PP-HEX-A and PP-HEX-B due to confidentiality. Furthermore, the testing is conducted in a temperature-controlled testing laboratory and the testing conditions are set according to the ISO standard. The preliminary testing results show that the temperature exchange efficiency and enthalpy exchange efficiency of the PP-HEXs have the same trends while the outdoor air temperature is fixed and varying the temperature of indoor air. In contrary, the temperature exchange efficiency and enthalpy exchange efficiency of the PP-HEXs have the same trends while the indoor air temperature is fixed and varying the temperature of outdoor air as well. With the default voltage supplies (240V) to VHR and the setup conditions (according to the ISO Standard) of return air to be 27°C and outdoor air to be 35°C, the testing results show that PP-HEX-A has a temperature exchange efficiency and enthalpy exchange efficiency with a range of (37.97 – 40.28) % and (30.77 – 57.81) % respectively. While PP-HEX-B has a temperature exchange efficiency and enthalpy exchange efficiency with a range of (35.29 – 42.5) % and (39.6 – 55.93) % respectively.
© The Authors, published by EDP Sciences, 2021
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.