Issue |
MATEC Web Conf.
Volume 268, 2019
The 25th Regional Symposium on Chemical Engineering (RSCE 2018)
|
|
---|---|---|
Article Number | 06006 | |
Number of page(s) | 6 | |
Section | Process for Energy and Environment | |
DOI | https://doi.org/10.1051/matecconf/201926806006 | |
Published online | 20 February 2019 |
Techno-economic analysis of a combined cooling, heating and power system based on hot sedimentary aquifer for hotel building in tropical countries
Department of Chemical Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok 16424 Indonesia
Corresponding author: widodo@che.ui.ac.id
Low enthalpy geothermal based Combined Cooling, Heating and Power (CCHP) system for building is expected can increase energy efficiency and reduce carbon dioxide emission. The aim of this study is to assess techno-economic performances of a CCHP for hotel building in tropical countries with total energy demand of 7.64 MW. The fresh geothermal fluid was divided by 15% to power generation system of Organic Rankine Cycle (ORC) and the waste heat merged with the rest fresh geothermal to absorption refrigeration system and heating systems. Cycle Tempo and COMSOL are used to simulate CCHP system and a borehole of hot sedimentary aquifer (HSA), respectively. The simulation results indicate that total CCHP system efficiency is 36.61% consist of ORC efficiency and absorption cycle efficiency are 12.77% and 57.88%, respectively with emission reduction of 1.4 ton CO2 eq. per year compare to conventional grid electricity. The best business scheme was BOO with financial incentives, which were tax allowance, soft loan, and grant. Therefore, the production prices were 0.08 USD/kWth, 0.10 USD/kWeh, and 12.03 USD/MMBtu for cooling, electricity, and heating respectively.
© The Authors, published by EDP Sciences, 2019
This is an open access article distributed under the terms of the Creative Commons Attribution License 4.0 (http://creativecommons.org/licenses/by/4.0), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.