Single-ended method to accurately calculate UHV AC transmission line frequency parameters
1
School of Electrical and Control Engineering, Xi’an University of Science and Technology, Yanta District, Xi’an, China
2
Electric Power Research Center, State Grid Shaanxi Electric Power Research Institute, Hangtian, Xi’an, China
* Corresponding author: 285103986@qq.com, 1311988379@qq.com
The power frequency parameter of transmission line is the basic parameter of line over-voltage calculation. It is necessary to get the parameters of 1000kV AC double-circuit line on the same tower in order to guide the operation of the project. In this paper, a method of accurately calculating UHV transmission line parameters is proposed. The length of the line is known, the voltage and current at the head of the line are measured, and the zero sequence, positive sequence total impedance and total capacitive reactance are obtained. Based on the distribution parameters Calculation formula, the line unit capacitance, resistance and inductance parameters can be obtained. The method of this paper is compared with the simulation of transmission line parameters in ATP simulation. And Through the actual measurement of the frequency parameters of Yu-heng 1000kV transmission line, it is verified that this method is suitable for the calculation of distribution parameters of UHV transmission lines.
© The Authors, published by EDP Sciences, 2018
This is an Open Access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.