Experimental Study on Performance of SF6+N2 Mixed Gas Insulation
1 Heilongjiang Electric Power Science Research Institude, Xiangjiang Road No.7, 150030 Harbin, Heilongjiang Province, China
2 Sulfur hexafluoride gas purification Laboratory of Analysis and Processing Technology of State Grid Corporation, Jinzhai Road No. 73, 230022 Hefei, Anhui Province, China
3 China ENFI Engineering Corporation, Fuxing Road No. 12, 100038 Beijing, China
a Corresponding author: 13163417178@163.com
This paper designed and constructed a 126kV GIS partial discharge test platform, performed frequency breakdown tests and lighting impulse tests at temperature of -30~20℃to SF6/N2 gas mixture. The present experiment studied frequency breakdown tests in different temperatue and slightly inhomogeneous electric field, obtained change in frequency breakdown voltage as a function of temperature; Analysed positive and negative lightning impluse test in gas mixture, in which SF6 had a propotion of 30%~60%, in different temperature. Results indicated 50% probability breakdown voltage variation in positive lightning impluse tests, and in a low temperature environment, the breakdown voltage increased at negative lightning impulse, the polarity effects varied with condition of pure SF6 gas. The experimental results showed implement of SF6/N2 mixed gas with 30% SF6 supersedespure SF6 gas, could effectively reduce the consume of SF6, and remit greenhouse efect.
© Owned by the authors, published by EDP Sciences, 2016
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.